UB10.241
24 V, 10 A for battery sizes from 3,9Ah to 40Ah
DC output | DC 24 V |
---|---|
10 A | |
Input | DC 24 V |
Dimensions (WxHxD) | 49 x 124 x 117 mm |
Weight | 530 g |
Input data
DC Input voltage | DC 24 V |
---|---|
Int. current consumption (incl. charging current) | 1.3 A |
Output data
Nominal voltage | 24 Vdc |
---|---|
22.5 Vds | |
Output current | 15 A |
10 A | |
Derating | 0.25 W/°C for >+60 °C |
Buffering
Storage element | External lead acid battery |
---|---|
Allowed battery size | 12 V, 3.9 to 40 Ah VRLA lead acid |
Temperature tracking of the end-of-charge voltage | manual-select |
Overview
Dimensions (WxHxD) | 49 mm x 124 mm x 117 mm |
---|---|
Weight per unit (excl. packaging) | 530 g |
Mounting method | DIN rail |
Operating temp. range | -25 °C to 70 °C |
Connection method | Spring clamps |
MTBF SN 29500 @ 40 °C (h) | 886000 h |
DC-OK signal | yes |