PISA-B-812-B4

Electronic circuit breaker
24 V, 40 A
8 output channels: 2x 1-12A, 6x 1-10A; Digital coded alarm signal
Datasheet
DC output DC 24 V
Input DC 19.2 V - 30 V
Dimensions (WxHxD) 52 x 124 x 130 mm
Weight 370 g
Compare

Input data

DC Input voltage DC 19.2 V - 30 V
DC Input current at no load, typ. 35 mA
Input voltage required to switch on the outputs, typ. 19 Vdc

Output data

Output current (sum of all outputs) 40 A
Turn-on delay of outputs 750 ms

Overview

Dimensions (WxHxD) 52 mm x 124 mm x 130 mm
Weight per unit (excl. packaging) 370 g
Mounting method DIN rail
Housing material Metal
Operating temp. range -25 °C to 70 °C
Connection method Push-in clamps
Power losses, typ. 10.8 W
No-load losses, typ. 1 W
MTBF SN 29500 @ 40 °C (h) 507000 h

PULS Services

User-friendly Assistance

PULS offers assistance on an individual level regarding your power supply selection. Online meetings can be arranged with our teams based in various international locations.

Application Support

PULS has successfully established an experienced team of application engineers to offer you the maximum technical support. They are always at your availability.

Delivery Reliability

PULS is deliberately working on guaranteeing the best delivery reliability. This guarantee is based on PULS controlling its full supply chain including the entire product life cycle.