XT40.241

DIN rail power supplies for 3-phase system
24V, 40A
semi-regulated
Datasheet
DC Output 24Vdc
40A
960W
Input AC 400V (± 15%)
Size (WxHxD) 96 x 124 x 159mm
Weight 1400g
Compare
Product Status: Stock item

Input Data

AC-Input Voltage AC 400V (± 15%)
Harmonic Correction active
Power Factor 0.93
Input Inrush Current Limitation active
Input inrush current 2A
External input fuse recommendation B-6A / C-3A

Output Data

Nominal voltage 24Vdc
Adjustment Range 24V
Output Current Range 40A
Output Current 40A at 24V
Output Power 960W
Power Reserves 25% power reserves
Ripple and noise voltage max. 1500mVpp

Overview

Size (WxHxD) 96mm x 124mm x 159mm
Weight per piece (excl. packaging) 1400g
Oper. temperature range -25°C to 70°C
Derating 24W/°C at >+60°C
Mounting Method DIN rail
Efficiency, typ. 95.5%
Power losses, typ. 45.2W
MTBF SN 29500 @ 40°C (h) 529000h
Connection method Screw terminals

PULS Services

User-friendly Assistance

PULS offers assistance on an individual level regarding your power supply selection. Online meetings can be arranged with our teams based in various international locations.

Application Support

PULS has successfully established an experienced team of application engineers to offer you the maximum technical support. They are always at your availability.

Delivery Reliability

PULS is deliberately working on guaranteeing the best delivery reliability. This guarantee is based on PULS controlling its full supply chain including the entire product life cycle.